Antw: [comis] COMIS - Atrium Simulation Questions

Dear Xu Peng

As mentioned by Marco, horizontal large openings are not included in
COMIS (yet).
I suggest to link the three atrium layers with normal crack links, but
assuming very low resistance, thus high C value and an exponent of 0.5

Any vertical temperature changes in the atrium can be considered in the
input temperature in the additional nodes.

Kind regards
Viktor Dorer



_______________________________________

Viktor Dorer
Dipl. Ing. ETH / ASHRAE, SAMPE
Head Energy Supply Technologies Group
Building Technologies Laboratory (118)
Empa - Materials Science & Technology
Ueberlandstrasse 129
CH-8600 Duebendorf Switzerland

Tel +41 44 823 42 75 / or ... 55 11
Fax +41 44 823 40 09
viktor.dorer@...
www.empa.ch

>>> Peng Xu <p.xu4@...> 02.10.2007 08:45 >>>
Dear "COMIS" users:
I am now trying to simulate the air-flow in an office building with
an
big atrium in the middle, with TRNSYS and COMIS. Because of the high
height and the temperature difference within the atrium, I divided the
atrium vertically into 3 zones, linking them with big openings as if
they
are fully linked and my concentrations for temperature will be on the
lowest level only.
But I got some strange answers from COMIS when I use the "large
opening"
air flow model between the zones of atrium. In my model, the offices
around the atrium will be mechanically ventilated and the atrium will
be
ventilated through adjacent air flows from the surrounding offices and
the air can be exhausted at the top of the atrium. I am not sure how
to
make such model with both mechanical ventilation and buoyancy
dominated
natural ventilation.
My concept for this study is hybrid ventilation. The external vents
for
offices would be on when conditions for natural ventilation are met. I
am quite appreciated if I can get help you and a sample COMIS .cpf
file
for the atrium or solar chimney will be highly useful for me to
understand.
Thanks very much in advance!

Best Regards,
Vince XU
the University of Melbourne,
Melbourne, Australia





Tue Oct 2, 2007 5:44 pm

viktor.dorer@...
Send Email Send Email

Forward
Message #782 of 862 |
Expand Messages Author Sort by Date

Dear "COMIS" experts: I am now trying to simulate the air-flow in an office building with an big atrium in the middle, with TRNSYS and COMIS. Because of the...
Peng XU
snowbirdxp
Offline Send Email
Sep 3, 2007
6:29 am

Dear "COMIS" users: I am now trying to simulate the air-flow in an office building with an big atrium in the middle, with TRNSYS and COMIS. Because of the high...
Peng Xu
snowbirdxp
Offline Send Email
Oct 2, 2007
6:48 am

dear Peng, I hope you can find mor detaild answar; I've been using comis in 2003-2004, to simulate a natural ventilated building with atrium to estract the...
marco massetti
massetmar
Offline Send Email
Oct 2, 2007
3:49 pm

Dear Xu Peng As mentioned by Marco, horizontal large openings are not included in COMIS (yet). I suggest to link the three atrium layers with normal crack...
Viktor Dorer
viktor.dorer@...
Send Email
Oct 2, 2007
5:44 pm

Dear Viktor and Macro: Thanks for your kind help, but in COMIS 3.1 User guide, I've found the following instructions in "&-WI (Windows and Doors)" : Slanted...
Vince(Peng) XU
snowbirdxp
Offline Send Email
Oct 4, 2007
6:17 am

May be it's right, actualy I don't know. In last period, I have not been working with comis best regards, marco "Vince(Peng) XU" <p.xu4@...>...
marco massetti
massetmar
Offline Send Email
Oct 5, 2007
4:43 pm

... As I understand it, to model the atrium, you want to draw an imaginary plane at some height, and then use that plane as a division between two imaginary...
David M. Lorenzetti
DMLorenzetti@...
Send Email
Oct 8, 2007
11:03 pm

Dear David: Thanks very much for your detailed explanation that COMIS is not capable to deal with air flows that are dominantly caused by buoyancy effect...
Vince(Peng) XU
snowbirdxp
Offline Send Email
Oct 8, 2007
11:41 pm

Vince, ... COMIS has, or used to have, an input section called &-NET-ZL (zone layers). This section allows you to prescribe variations of temperature (and...