Dear Mohamed
Comis schedules are not working in coupled comis-trnsys projects. All
time depending variables of comis have to be declared as inputs and
must be determined outside of comis with the help of an other trnsys
type or an equation. e.g room temperatures are usually calculated by
the thermal building model type 56. If you need fixed schedules, use the
time depending forcing function type 14 or define your schedule in a
separate file and use the data reader type 9.
regards,
Andreas
Building Technologies
Empa - Materials Science & Technology
Überlandstrasse 129
CH-8600 Dübendorf
Tel. ++41 ( 0)44 823 47 22
FAX ++41 (0)44 823 40 09
andreas.weber@...
www.empa.ch
>>> mohamed hassaan <mamado_00@...> 30.12.2008 02:10 >>>
my dear
I need help
In the coupeled projects (comis-trnsys) how can I defined a temperature
schedule
and can I defined a hourly temperature schedule for three months
yours
mohamed