Hello, I am currently doing a simulation coupling trnsys and comis and i get two times the following error on comis: the maximum number of iteration steps has...
elisabethaslanian
elisabethasl...
Offline Send Email
Jul 12, 2006
7:20 pm
595
... Here are some simple things to try, all in the &-PR-CONT section of the input file: (1) Increase the "max number of iterations allowed" e.g. from 500 to ...
David M. Lorenzetti
DMLorenzetti@...
Send Email
Jul 12, 2006
8:51 pm
596
Thank you for your prompt reply! I have run my simulation after increasing the number of iterations ( from 1000 to 1000000) and I have mot anymore my previous...
aslanian elisabeth
elisabethasl...
Offline Send Email
Jul 12, 2006
9:55 pm
597
Elisabeth, Could you send us the complete error message (or the entire list file), please ? This sounds like a TRNSYS error, but I'm not quite sure... Werner ...
keilholz, werner
wkeilholz
Offline Send Email
Jul 13, 2006
7:23 am
599
Dear COMIS user, TRNSYS 16.1 allows to create 2 new project types : « COMIS Project » and « Coupled Project ». A limited version of the COMIS simulator is ...
cstb_software
Offline Send Email
Jul 20, 2006
12:42 pm
600
Hi all, I'm using COMIS excel to do multiple runs and I want to choose the standard Monte Carlo or discrete parametric analysis (by leaving D13 empty) but the...
Mike.Deevy@...
Send Email
Jul 25, 2006
4:36 pm
601
Hi all, I'm using COMIS excel to do multiple runs and I want to choose the standard Monte Carlo or discrete parametric analysis (by leaving D13 empty) but the...
Mike.Deevy@...
Send Email
Jul 26, 2006
7:19 am
602
Papers are sought for the following two transactions planned for the Long Beach (Summer 2007) ASHRAE meeting. Papers are due by September 29, 2006. Coupling...
wsdols
Offline Send Email
Jul 26, 2006
1:01 pm
606
Hello Users, I am having difficulty understanding the output of COMIS regarding timesteps. For instance, my START is 1993may01_01:10 and STOP is ...
Lisa
china4ever2003
Offline Send Email
Aug 31, 2006
4:23 pm
607
Regarding your pollutant stepping question, the answers below are correct for the old public-domain version of COMIS (3.0.2). They probably hold as well for...
David M. Lorenzetti
DMLorenzetti@...
Send Email
Aug 31, 2006
4:58 pm
609
In section "3.5 Modelling Concepts" of COMIS User Guide 3.1 and 3.2 is a subsection "Schedules, Time Steps and Simulation Dynamics" which explains in detail...
Andreas Weber
andreas_webe...
Offline Send Email
Sep 4, 2006
6:40 am
610
Thanks so much for the help. I was able to implement POLSTEP using 3.2 with simulation studio. How do I specify that I want to save -S the concentration in...
Lisa
china4ever2003
Offline Send Email
Sep 8, 2006
6:40 pm
611
Hello, When I input this, for instance: FL-S hf_4 hf_5 hf_6 hf_13 hf_14 hf_15 hf_22 hf_23 hf_24 hf_31 hf_32 hf_33 hf_40 hf_41 hf_42 I get an error b/c the...
Lisa
china4ever2003
Offline Send Email
Sep 13, 2006
2:15 pm
612
Try: FL-S hf_4-hf_42 This will output the flow of all the links which are defined between hf_4 and hf_42 in the link list under &-NET-LINKs including the flow...
Andreas Weber
andreas_webe...
Offline Send Email
Sep 15, 2006
6:30 am
620
Hello group Under &-WI, what is the value for Cs for open doors? Cs is defined as flow coefficient for close windows per m crack length. If the door or window...
Lisa
china4ever2003
Offline Send Email
Oct 16, 2006
9:23 pm
621
... The Cs value (in the second row of the *W block) describes the window/door leakage when it is closed. As the window/door opens, the airflow is determined...
David M. Lorenzetti
DMLorenzetti@...
Send Email
Oct 16, 2006
10:00 pm
622
Thank you, your response was of great help. I am modeling a type 1 WI so won't need to know how the opening fraction is used here. Thanks again for the quick...
Lisa
china4ever2003
Offline Send Email
Oct 17, 2006
1:32 pm
626
Dear sir I have download the software of COMIS 3.0 with IISiBat from http://evl.cstb.fr/francais/projets/IISiBat/COMIS/confcom.htm. When I run the software, it...
kwanghvacr
Offline Send Email
Oct 25, 2006
7:32 am
627
As far as I know, this version does not run on Windows XP. I guess that might be the problem. Nicolas Heijmans Belgian Building Research Institute (CSTC - WTCB...
Nicolas Heijmans
heijmansnicolas
Offline Send Email
Oct 26, 2006
9:06 am
629
COMIS 3.1 does run on Windows XP, as well as its graphical interface. But you should not use the old (outdated link) to access it. The right link is ...
keilholz, werner
wkeilholz
Offline Send Email
Oct 30, 2006
8:43 am
631
dear Werner and Nicolas Heijmans Thank you very much for your responds. I have download the COMIS 3.2 from http://software.cstb.fr/soft/present.asp?langue=us....
kwanghvacr
Offline Send Email
Oct 31, 2006
2:33 am
632
The older versions of COMIS also run on XP, as far as the kernel is concerned. The graphical User Interface, however, does not run on XP. You could try to use...
keilholz, werner
wkeilholz
Offline Send Email
Oct 31, 2006
8:37 am
633
Hi there: I found this mistake message: the pollutant name co2 in schedule Qco2 matches none of the pollutants. Correct the input at &-NET-ZONE or &-POL-DES...
cainabj
Offline Send Email
Oct 31, 2006
8:41 am
635
Dear all: I read about the content on histograms in the Comis user guide, but I wonder how I can difine the histograms in simulation studio? Thanks a lot!...
cainabj
Offline Send Email
Nov 1, 2006
6:01 am
636
Dear all: I read about the content on histograms in the Comis user guide, but I wonder how I can difine the histograms in simulation studio? Thanks a lot!...
cainabj
Offline Send Email
Nov 1, 2006
6:02 am
637
In the Studio, you define histograms in the 'Control Cards' (Control Card button or 'Assembly/Control Cards...' menu): Go to the Schedules/Layers/Occupants...
keilholz, werner
wkeilholz
Offline Send Email
Nov 2, 2006
9:18 am
640
Dear COMIS group member I'm Fujikawa at Yoshino lab of Tohoku University Japan. I have a question about contaminant calculation. Sorry for my poor English. My...
Mitsutoshi Fujikawa
us.light_wis03
Offline Send Email
Nov 8, 2006
7:34 am
641
Hello, Mitsutoshi, You can try our model COwZ (COMIS with sub-zones). There are no limits for the zone number. You can also get details of airflows,...
Zhengen Ren
zren401
Offline Send Email
Nov 8, 2006
9:47 am
644
Dear COMIS users It is written on the user's guide that some couple of data(pressure and airflow rate) can be used as the performance of a fan. And it seems...
skcomis
Offline Send Email
Nov 17, 2006
3:20 am
646
Hello, I don 't know TRNFLOW, but if its like in COMIS, fans are defined by a fan curve. There are two ways of doing this, either by giving data pairs or ...